Agrostroj Pelhřimov
20 DALI routers
1280 DALI addresses and 32 circuits
80 independent
working areas
Central
lighting sensor with tailor-made visualisation
There are movement sensors for dimming rack isles installed in the warehouses. All of that is managed by the power engineer via visualisation and configuration software. The maintenance for localisation and identification of defects uses a special visualisation for individual light fixture control performed via a mobile phone or a tablet. For example, the lighting system in the dispatch hall is set to turn off the lights automatically when the daily illuminance of the area reaches the required level.
The level of illuminance must be the same or higher for a period of one hour to prevent unnecessary flickering of the lighting system. When the sun sets, the night lights are activated automatically in those parts of the hall where the main lights are off. The automatic night lighting is switched off after dawn. The lighting only switches off in areas where work lighting is not activated. The user is trained at a higher level of knowledge and he or she can execute changes and configurations of the lighting system settings.